Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the wishlist-member domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home1/prachvac/public_html/wp-includes/functions.php on line 6114

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the loginizer domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home1/prachvac/public_html/wp-includes/functions.php on line 6114

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the wordpress-seo domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home1/prachvac/public_html/wp-includes/functions.php on line 6114

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the astra domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home1/prachvac/public_html/wp-includes/functions.php on line 6114

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the astra-addon domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home1/prachvac/public_html/wp-includes/functions.php on line 6114
BCA Part J5.4 Fan systems​

J5.3 Mechanical ventilation system control

J5.3 Mechanical ventilation system control

(a) General — A mechanical ventilation system, including one that is part of an air-conditioning system, except where the mechanical system serves only one sole-occupancy unit in a Class 2 building or serves only a Class 4 part of a building, must—
[It is applicable for mechanical ventilation which may be part of an air-conditioning system or a separate system such as a car park mechanical ventilation system.]

(i) be capable of being deactivated when the building or part of the building served by that system is not occupied; and
[If the mechanical ventilation system only serves a single floor, when that floor is unoccupied, then it must be capable of being stopped.]

(ii) when serving a conditioned space, except in periods when evaporative cooling is being used—

(A) where specified in Table J5.3, have—
[Where it is specified in Table J5.3; either modulating control or energy reclaiming system to be installed.]

(aa) an energy reclaiming system that preconditions outdoor air at a minimum sensible heat transfer effectiveness of 60%; or
(bb) demand control ventilation in accordance with AS 1668.2 if appropriate to the application; and

(B) not exceed the minimum outdoor air quantity required by Part F4 by more than 20%, except where—
[It is with an exception for evaporative air-conditioning and the criteria below

(aa) additional unconditioned outdoor air is supplied for free cooling; or
(bb) additional mechanical ventilation is needed to balance the required exhaust or process exhaust; or
(cc) an energy reclaiming system preconditions all the outdoor air; and

 (iii) for an airflow of more than 1000 L/s, have a variable speed fan unless the downstream airflow is required by Part F4 to be constant.
[It is prescribed where possible that larger mechanical ventilation systems have a variable speed fan.]

oa controls

Table J5.3 Required outdoor air treatment

(b) Exhaust systems — An exhaust system with an air flow rate of more than 1000 L/s must be capable of stopping the motor when the system is not needed, except for an exhaust system in a sole-occupancy unit in a Class 2, 3 or 9c building.
[They are taking, for example of kitchen exhaust and laundry systems. Minimum ventilation rates take precedence over energy efficiency measures.

(c) Carpark exhaust systems — Carpark exhaust systems must have a control system in accordance with—
[It requires car park exhaust systems to have carbon monoxide monitoring, according to AS1668.2.]

(i) 4.11.2 of AS 1668.2; or
(ii) 4.11.3 of AS 1668.2.

(d) Time switches—

(i) A time switch must be provided to a mechanical ventilation system with an air flow rate of more than 1000 L/s.
[Need to comply with Specification J6]

(ii) The time switch must be capable of switching electric power on and off at variable pre-programmed times and on variable pre-programmed days.
(iii) The requirements of (i) and (ii) do not apply to—

(A) a mechanical ventilation system that serves—

(aa) only one sole-occupancy unit in a Class 2, 3 or 9c building; or
(bb) a Class 4 part of a building; or

(B) a building where mechanical ventilation is needed for 24 hour occupancy. 